DGX B200's 14.3 kW ceiling is 1.79 kW for each of its 8 GPUs

DGX B200 lists ~14.3 kW max for a chassis of 8 Blackwell GPUs. That is 1.79 kW per GPU against the 700 W ceiling printed on H100 and H200 SXM boards.

Verified answer checked

NVIDIA's DGX B200 page lists System Power Usage as ~14.3 kW max for a chassis with 8x NVIDIA Blackwell GPUs. Divided eight ways that is 1.79 kW per GPU, or 1,787.5 W (calculated 2026-11-16). The H100 and H200 pages both print a maximum thermal design power of Up to 700W, configurable, for their SXM parts, so the per-GPU share of a DGX B200 works out at 2.55 times the older board label (calculated 2026-11-16). The two figures measure different things: 700 W is a device ceiling, while 14.3 kW is the whole chassis including 2 Intel Xeon Platinum 8570 processors, 2 TB of memory and 8x 3.84 TB NVMe drives (checked 2026-11-16).

  • NVIDIA's DGX B200 page lists System Power Usage as ~14.3 kW max, in a chassis whose GPU row reads 8x NVIDIA Blackwell GPUs (checked 2026-11-16).
  • The same table lists 2 Intel Xeon Platinum 8570 Processors with 112 cores total, 2 TB of system memory configurable to 4 TB, and 8x 3.84 TB NVMe U.2 drives (checked 2026-11-16).
  • H100 and H200 both print a maximum thermal design power of Up to 700W, configurable, in their SXM columns, while H100 PCIe prints 350-400W and H200 PCIe prints Up to 600W (checked 2026-11-16).
  • 14.3 kW divided by 8 GPUs is 1.79 kW per GPU, or 1,787.5 W, which is 2.55 times the 700 W label on an SXM Hopper board (calculated 2026-11-16).
  • Eight 700 W boards sum to 5.6 kW, so 8.7 kW of the 14.3 kW ceiling belongs to everything in the chassis that is not a GPU (calculated 2026-11-16).
  • Per kilowatt the chassis yields 0.56 GPUs, against 1.43 GPUs per kilowatt for a 700 W board standing alone (calculated 2026-11-16).

3 primary sources · If this is out of date, tell us and we will re-measure.

On this page
  1. What the power row prints
  2. Dividing 14.3 kW by eight
  3. Why 1.79 kW is not a 1,787 W GPU
  4. How we verified this

A GPU power figure is a device ceiling. A system power figure is a chassis ceiling. The DGX B200 page publishes the second one and leaves the reader to divide it, while the H100 and H200 pages publish the first. Putting 1.79 kW next to 700 W is arithmetic, not a like-for-like measurement, and the gap between them is the rest of the machine.

What the power row prints

The DGX B200 specification table gives System Power Usage as ~14.3 kW max. The same table gives the GPU row as 8x NVIDIA Blackwell GPUs, and then names what else is plugged in: 2 Intel Xeon Platinum 8570 Processors, 112 Cores total, 2 TB of system memory configurable to 4 TB, 8x 3.84 TB NVMe U.2 drives on top of two 1.9 TB boot drives, 4x OSFP ports serving 8x single-port ConnectX-7 adapters, and 2x dual-port BlueField-3 DPUs. Rack height is 10 RU.

The Hopper pages publish the other kind of number. H100 and H200 both list a maximum thermal design power of Up to 700W, configurable, in their SXM columns. Their PCIe columns read differently: 350-400W on H100, Up to 600W on H200.

Dividing 14.3 kW by eight

14.3 kW over 8 GPUs is 1.7875 kW per GPU, reported as 1.79 kW or 1,787.5 W (calculated 2026-11-16). Against the 700 W board label that is 2.55 times the power for one device slot (calculated 2026-11-16).

ItemValueWhere it comes from
DGX B200 system power~14.3 kW maxDGX B200 spec table
DGX B200 GPU count8x NVIDIA BlackwellDGX B200 spec table
Power per GPU slot1.79 kW14.3 kW ÷ 8 (calculated 2026-11-16)
H100 SXM power ceilingUp to 700W, configurableH100 spec table
H200 SXM power ceilingUp to 700W, configurableH200 spec table
Ratio per slot2.55x the 700 W label1,787.5 ÷ 700 (calculated 2026-11-16)
Eight 700 W boards5.6 kW8 × 700 W (calculated 2026-11-16)
Non-GPU share of the chassis8.7 kW14.3 kW − 5.6 kW (calculated 2026-11-16)
GPUs per kilowatt0.568 ÷ 14.3 (calculated 2026-11-16)

Why 1.79 kW is not a 1,787 W GPU

The division puts every watt of the chassis on the GPU row, and the chassis is not just GPUs. Subtract eight 700 W boards from 14.3 kW and 8.7 kW is left for two processors, 2 TB of memory, ten NVMe drives, the DPUs, the fans and the conversion losses in the power supplies (calculated 2026-11-16). That 8.7 kW is larger than the eight boards' own 5.6 kW.

So the honest reading is a budget ratio, not a device rating: for every GPU slot a facility has to provision 1.79 kW of capacity. Rate-of-change matters less than the total here, because the number a data hall needs is the number on the breaker.

The practical consequence is density. At 14.3 kW per 10 RU chassis, a 30 kW allocation holds two systems with 1.4 kW left over, and a 100 kW allocation holds six (calculated 2026-11-16). The same 100 kW spent on bare 700 W boards buys 143 device slots on paper (calculated 2026-11-16), which is the kind of figure a spec sheet invites and a floor plan refuses: those boards still need hosts, NICs, memory and cooling.

There is a second caveat in the label itself. The tilde in ~14.3 kW max marks a nominal maximum, and the row carries no measured draw, no idle figure and no per-workload curve. H100 and H200, by contrast, print a configurable ceiling that an operator can set lower.

How we verified this

The three pages were fetched on 2026-11-16 and the power rows were read from the specification tables rather than from the prose. The arithmetic keeps the printed precision: 14.3 divided by 8 is 1.7875, and 1,787.5 divided by 700 is 2.554.

The figures 14.3, 8, 700, 350-400, 600, 112, 2 and 4 all appear on the cited pages and are marked checked. The per-slot power, the ratios, the sums and the per-kilowatt rates are derived and are marked calculated. If any of the two vendors revises a power row, both the per-slot figure and the ratio move, which is why every value in the table carries the day it was read.

Frequently asked questions

Does 1.79 kW mean each GPU in a DGX B200 draws 1,787 W?

No. The page publishes one power figure for the whole system and one GPU count, so the division is a share of the chassis budget rather than a device measurement. No per-GPU thermal design power appears on the DGX B200 page at all, which is why this article divides instead of quoting.

Why is the chassis figure 2.55 times the sum of the GPU labels?

Because the 14.3 kW row covers more than accelerators. The same table lists two Xeon Platinum 8570 processors, 2 TB of DDR5, eight 3.84 TB NVMe drives, four OSFP ports with ConnectX-7 adapters, two BlueField-3 DPUs, six fan trays worth of airflow and the losses inside the power supplies.

What is left out of the 14.3 kW?

Everything past the wall. Facility cooling, the PDU and its breaker, cable losses and the headroom a circuit needs are all outside the number, and the tilde in ~14.3 kW signals that the figure itself is a nominal maximum rather than a measured draw.

How many fit in a fixed power allocation?

At 14.3 kW each, two systems need 28.6 kW, which leaves 1.4 kW of a 30 kW allocation for everything else (calculated 2026-11-16). A 100 kW allocation reaches 6 systems, and by the per-kilowatt rate that is 0.56 GPUs per kilowatt, against 1.43 GPUs per kilowatt for bare 700 W boards (calculated 2026-11-16).

Sources

  1. NVIDIA DGX B200System Power Usage ~14.3 kW max, 8x Blackwell GPUs, 2 Xeon 8570 processors, 2 TB memory, 8x 3.84 TB NVMe, 10 RU; checked 2026-11-16
  2. NVIDIA H100 Tensor Core GPUMax Thermal Design Power rows: Up to 700W configurable on SXM, 350-400W configurable on PCIe; checked 2026-11-16
  3. NVIDIA H200 Tensor Core GPUMax Thermal Design Power rows: Up to 700W configurable on SXM, Up to 600W configurable on PCIe; checked 2026-11-16

Cite this page

Nadia Voss (2026). “DGX B200's 14.3 kW ceiling is 1.79 kW for each of its 8 GPUs”. Actual Database. https://actualdatabase.com/dgx-b200-power-per-gpu/

Written and verified by

Nadia Voss · Data researcher

I collect prices, limits and quotas from primary sources, date every figure, and re-check them on a fixed schedule. No sponsored placements inside a table, ever.